feat(pipeline): PLC/SPS control-logic security scanner (IEC 61131-3)
CI / Check (pull_request) Failing after 2m31s
CI / Detect Changes (pull_request) Has been skipped
CI / Deploy Agent (pull_request) Has been skipped
CI / Deploy Dashboard (pull_request) Has been skipped
CI / Deploy Docs (pull_request) Has been skipped
CI / Deploy MCP (pull_request) Has been skipped
CI / Check (pull_request) Failing after 2m31s
CI / Detect Changes (pull_request) Has been skipped
CI / Deploy Agent (pull_request) Has been skipped
CI / Deploy Dashboard (pull_request) Has been skipped
CI / Deploy Docs (pull_request) Has been skipped
CI / Deploy MCP (pull_request) Has been skipped
Implements ScanType::PlcControlLogic — the missing piece for PlcSps targets, which previously classified but ran no scan. New `pipeline::plc`: - A real IEC 61131-3 Structured Text front end: lexer + recursive-descent parser → AST (POUs, typed VAR sections, statements, expressions). Tolerant recovery so odd constructs never sink a file. - PLCopen XML extractor: pulls each ST POU's interface vars + `<ST>` body and reconstructs equivalent ST, so raw `.st` files and PLCopen projects share one analysis path. - Eight semantic, guard-aware rules over the AST → findings: hardcoded credentials, default/weak passwords, safety-interlock/watchdog bypass, array indexed by unvalidated input, division without a zero-guard (suppressed when an enclosing `IF <d> <> 0` proves it), insecure comm (auth/encryption disabled), and cleartext OT protocol ports, plus unstructured JMP. Each carries CWE + remediation. - `PlcControlLogicScanner` (Scanner impl) walks the project tree and emits `Finding`s (dedup fingerprint, file, line, severity). Wired into `run_target_pipeline`: when the scan plan includes PlcControlLogic, `run_plc_scan` ingests the PlcProject artifact, analyzes it, and persists the findings (findings_count handled by run_target). Demo fixtures under examples/plc-demo/ (a vulnerable pump-station `.st` + a PLCopen `conveyor.xml`). Tests: parser, all-rules-fire, guarded-clean-is-quiet, and an end-to-end tree scan — 5 passing. Adds `roxmltree` (read-only XML) for PLCopen parsing. Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
This commit is contained in:
co-authored by
Claude Opus 4.8
parent
a981311413
commit
fcd49ecdf7
@@ -0,0 +1,36 @@
|
||||
<?xml version="1.0" encoding="utf-8"?>
|
||||
<!-- Demo PLCopen project — conveyor sorter. Deliberately vulnerable. -->
|
||||
<project xmlns="http://www.plcopen.org/xml/tc6_0201">
|
||||
<types>
|
||||
<pous>
|
||||
<pou name="ConveyorCtrl" pouType="program">
|
||||
<interface>
|
||||
<localVars>
|
||||
<variable name="AdminPwd">
|
||||
<type><string/></type>
|
||||
<initialValue><simpleValue value="password"/></initialValue>
|
||||
</variable>
|
||||
<variable name="Belt">
|
||||
<type>
|
||||
<array>
|
||||
<dimension lower="0" upper="3"/>
|
||||
<baseType><INT/></baseType>
|
||||
</array>
|
||||
</type>
|
||||
</variable>
|
||||
</localVars>
|
||||
<inputVars>
|
||||
<variable name="Slot"><type><INT/></type></variable>
|
||||
</inputVars>
|
||||
</interface>
|
||||
<body>
|
||||
<ST>
|
||||
<xhtml xmlns="http://www.w3.org/1999/xhtml">Belt[Slot] := 1;
|
||||
Ftp_Send(HOST := '192.168.1.5', PORT := 21, ENCRYPT := FALSE);
|
||||
</xhtml>
|
||||
</ST>
|
||||
</body>
|
||||
</pou>
|
||||
</pous>
|
||||
</types>
|
||||
</project>
|
||||
@@ -0,0 +1,57 @@
|
||||
(*
|
||||
* Demo PLC program — pump-station control (IEC 61131-3 Structured Text).
|
||||
*
|
||||
* Deliberately vulnerable, for the compliance-scanner PLC control-logic demo.
|
||||
* Each issue below is flagged by pipeline::plc::rules.
|
||||
*)
|
||||
|
||||
FUNCTION_BLOCK PumpStationCtrl
|
||||
VAR_INPUT
|
||||
OperatorCmd : INT; (* HMI command index — untrusted *)
|
||||
FlowSetpoint : REAL;
|
||||
END_VAR
|
||||
VAR_OUTPUT
|
||||
PumpSpeed : REAL;
|
||||
Fault : BOOL;
|
||||
END_VAR
|
||||
VAR
|
||||
HmiPassword : STRING := 'admin123'; (* hardcoded + default credential *)
|
||||
ApiKey : STRING := 'sk_live_9c1f2a'; (* hardcoded secret *)
|
||||
PumpProfiles : ARRAY[0..7] OF REAL;
|
||||
Safety_Enable : BOOL := TRUE;
|
||||
Watchdog_Kick : INT := 1;
|
||||
MeasuredFlow : REAL;
|
||||
ScaleFactor : REAL;
|
||||
i : INT;
|
||||
END_VAR
|
||||
|
||||
(* Operator can index the profile table with an unvalidated command. *)
|
||||
PumpSpeed := PumpProfiles[OperatorCmd];
|
||||
|
||||
(* Divisor is a live process value that can read zero on a stopped line. *)
|
||||
ScaleFactor := FlowSetpoint / MeasuredFlow;
|
||||
|
||||
(* Safety interlock disabled straight from application logic. *)
|
||||
IF OperatorCmd = 99 THEN
|
||||
Safety_Enable := FALSE;
|
||||
Watchdog_Kick := 0;
|
||||
END_IF;
|
||||
|
||||
(* Unauthenticated Modbus/TCP link on the cleartext OT port. *)
|
||||
Modbus_TCP_Connect(IP := '10.10.5.20', PORT := 502, AUTH := FALSE, PASSWORD := 'plc');
|
||||
|
||||
(* Unstructured jump around the fault handler. *)
|
||||
IF MeasuredFlow > 1000.0 THEN
|
||||
JMP trip;
|
||||
END_IF;
|
||||
|
||||
(* A correctly guarded division — must NOT be flagged. *)
|
||||
IF ScaleFactor <> 0.0 THEN
|
||||
PumpSpeed := PumpSpeed / ScaleFactor;
|
||||
END_IF;
|
||||
|
||||
RETURN;
|
||||
trip:
|
||||
Fault := TRUE;
|
||||
PumpSpeed := 0.0;
|
||||
END_FUNCTION_BLOCK
|
||||